fieldcommunicator

Yokogawa AAB141-S50/K4A00 Analog Input Module AAB141-H53/K4A

Yokogawa AAB141-S50/K4A00 Analog Input Module AAB141-H53/K4A00 Arrived

 

Yokogawa AAB141-S50/K4A00 Analog Input Module AAB141-H53/K4A00 Arrived

 

Model and Suffix Codes of AAB141

 

 

   

Description

Model

AAB141

Analog Input Module (1 to 5 V/4 to 20 mA, 16-channel, Non-Isolated)

 

 

Suffix Codes

-H

With digital communication (HART protocol)

5

With no explosion protection

E

With explosion protection

0

Basic type

3

With ISA Standard G3 option and temperature (-20 to 70 °C) option

Option Codes

/K4A00

With KS Cable Interface Adapter [Model: ATK4A-00]

 

External Dimensions of AAB141

 

image

 

 

n STANDARD SPECIFICATIONS
 

l Current/Voltage Input Modules (Non-Isolated)
 

These modules provide 16 inputs of mainly 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire/4-wire transmitters.

They can be used in dual-redundant configuration.

 

Items

Specifications

Model

AAI141 (*1)

AAV141

AAV142

AAB141(*1) (*4)

Number of input channels

16, non-isolated

16, non-isolated   (differential input)

16, non-isolated

16, non-isolated

When the voltage input is

selected the differential input is applied.

 

Input signal

4 to 20 mADC

1 to 5 V DC

(allowable common mode voltage ± 1 V or less)

-10 to 10 V DC

Voltage input : 1to 5 V DC

(allowable common mode voltage ±1 V or less)

Current input : 4 to 20 mADC(*5)

Allowable input current/voltage

27 mA

±7.5 V

±13 V

Voltage input : ±7.5 V

Current input : 25 mA

Withstanding voltage

 

Input resistance

Power ON

400 Ω (at 20 mA) to    1000 Ω (at 4 mA) (*2)

1 MΩ or larger

1 MΩ or larger

Voltage input : 1 MΩ or larger

Current input : 290 Ω (at 20 mA) to 450 Ω (at 4 mA) (*6)

Power OFF

500 kΩ or larger

340 kΩ or larger

660 kΩ or larger

Voltage input : 340 kΩ or larger

Current input : 500 kΩ or larger

Accuracy

±16 µA

±4 mV

±20 mV

Voltage input : ±4 mV

Current input : ±16 μA

Data update period

10 ms

Step response time

100 ms

 

Transmitter power supply

14.8 V or higher (at 20 mA) (*3)

26.4 V or less (at 0 mA)     (output current limit: 27 mA)

 

Setting of 2-wire or 4-wire transmitter

For each channel by setting pin

Drift due to ambient  temperature change

±16 µA/10 °C

±4 mV/10 °C

±20 mV/10 °C

±0.1 %/10 °C

Maximum current consumption

310 mA (5 V DC),

450 mA (24 V DC)

350 mA (5 V DC)

350 mA (5 V DC)

480 mA (5 V DC),

120 mA (24 V DC)

Weight

0.2 kg

0.2 kg

0.2 kg

0.3 kg

External connection

Pressure clamp terminal, KS cable, MIL connector cable

KS cable

HART communication (*7)

Available

Available (at current input)

 

 

More Yokogawa AAB141 Analog Input Module (1 to 5 V/4 to 20 mA, 16-channel, Non-Isolated):

 

 

 

 

 

 

 

AAB141-S50/K4A00

 

AAB141-S53/K4A00

 

AAB141-SE0/K4A00

 

AAB141-SE3/K4A00

 

AAB141-H50/K4A00

 

AAB141-H53/K4A00

 

AAB141-HE0/K4A00

 

AAB141-HE3/K4A00

 

 

We mainly supply Siemens, Schneider, Honeywell, ABB, Allen Bradley, Mitsubishi, Omron, Eaton, Pepperl+Fuchs, MTL, Phoenix Contact,Weidmuller, Festo, IFM, Wago, Pilz, Degson, Sick, SMC, Norgren, Yokogawa, Yaskawa, Fluke, SEW, Emerson,Endress+Hauser,Vega, Hirschmann,Moxa, CISCO, Turck, Beckhoff, B&R, Balluff, Bifold, GE,Rittal, Proface, Wintek,Danfoss,EBM, YTC,Hach,Delta, Finder,Wohner, CHINT, Autonics,Testo, Bently Nevada, PR Electronics, Meanwell, Dell and so on.

 

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.

 