fieldcommunicator

MTL5582 Resistance Isolator MTL5582 Safety Barriers Original

description:MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New...
BASIC INFO

MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New


 




Temperature Input module of MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New

These modules accept inputs from low-level dc sources such as thermocouples or RTDs in hazardous
areas and converts them into 4/20mA signals to drive safe area loads.

Early burnout detection (EBD) of 
MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New

When EBD is selected, the resistance of the thermocouple circuit is monitored and an alarm is
raised when there is an increase of more than 50m. This enables preventative maintenance to be
conducted on the field installation before the thermocouple actually breaks.

Configuration using PCS45/PCL45USB of 
MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New

Use PCS45 software, in conjunction with the PCL45USB serial link, to configure these modules. Instructions
are contained within the software.

 

MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New

Single channel, to repeat RTD signals

The MTL5582 connects to a 2-, 3-, or 4-wire resistance temperature device (RTD) or other resistance
located in a hazardous area, isolates it and repeats the resistance to a monitoring system in the safe
area. The module is intended typically (but not exclusively) for use with Pt100 3-wire RTDs. Switches
enable selection of 2-, 3-, or 4-wire RTD connection. The MTL5582 should be considered as an
alternative, non-configurable MTL5575, for use in RTD applications where a resistance input is
preferred or needed instead of 4/20mA. The design is notable for its ease of use and repeatability.
The number of wires which can be connected on the safe-area side of the unit is independent of the
number of wires which can be connected on the hazardous-area side. The module drives upscale
in the case of open circuit detection.


MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New
 

•Compact modular design with DIN rail mounting

•High packing density

•Single and multi-channel I/O modules

•3-port isolation with low power dissipation

•Compatible with MTL5000


MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New

Part Number of MTL5500 Series  

MTL5501-SR, MTL5510, MTL5510B, MTL5511, MTL5513, MTL5514, MTL5514D, MTL5516C, MTL5517, MTL5521, MTL5522, MTL5523, MTL5523V, MTL5523VL, MTL5524, MTL5525, MTL5526, MTL5531, MTL5532, MTL5533, MTL5541, MTL5541A, MTL5541AS, MTL5541S, MTL5544, MTL5544A, MTL5544AS, MTL5544D, MTL5544S, MTL5546, MTL5546Y, MTL5549, MTL5549Y, MTL5561, MTL5575, MTL5576-RTD, MTL5576-THC, MTL5581, MTL5582

MTL5582 Resistance Isolator MTL5582 Safety Barriers Original New
 

MTL5000 Function MTL5500 Notes
MTL5011B 1ch, changeover relay output MTL5511  
MTL5012 1ch, solid-state output   Use 1ch of MTL5513
MTL5012S 1ch, solid-state output, UE1 special   No replacement
MTL5014 1ch, c/o relay output, LFD relay MTL5514/14D MTL5514 does not provide 1in 2out
function. MTL5514D with 1in 2out
available Q1 2014
MTL5015 2ch, solid-state output MTL5513 Common connection on haz side,
max frequency response 500Hz
MTL5016 2ch, n/o relay output MTL5516C  
MTL5017 2ch, n/o relay output, LFD relay MTL5517 LFD relay energises on alarm
MTL5018 2ch, changeover relay output MTL5516C Common connection on haz side
MTL5018ac 2ch, changeover relay output, ac power   Continues as MTL5018ac.
Alternative option: MTL5516C fitted
with MPA5500 ac adaptor
MTL5021 Loop powered, IIC, (12.85V, 45mA, cl 45mA) MTL5521 (12.8V, 48mA, cl 48mA)
MTL5022 Loop powered, IIB, (12.9V, 60mA, cl 60mA) MTL5522 (9.9V, 70mA, cl 70mA)
MTL5023 Logic ctrl, lfd, phase,(12.85V, 45mA, cl 45mA) MTL5523 (12.8V, 48mA, cl 48mA)
MTL5024 Logic ctrl, phase, (12.85V, 45mA, cl 45mA) MTL5524 (12.8V, 48mA, cl 48mA)
MTL5025 Loop powered, IIC, (8.6V, 45mA, cl 45mA) MTL5525 (7V, 48mA, cl 48mA), lower Io
MTL5031 Vibration transducer interface MTL5531 Now Velomitor compatible
MTL5032 Pulse isolator MTL5532 Now with 4-20mA output and alarm
MTL5040 Loop isolator   Use MTL5541 and MTL5546Y
MTL5041 For 2-wire transmitters MTL5541  
MTL5042 For 2- or 3-wire txs, smart MTL5541  
MTL5043 Dual output for 2-wire smart txs MTL5544D No current sink o/p. Passive Tx input
MTL5044 Two channel for 2-wire txs MTL5544 Now with passive Tx inputs
MTL5045 Isolating driver MTL5546Y Smart only versions
MTL5046 Smart isolating driver with LFD MTL5546  
MTL5049 Two channel isolating driver MTL5549Y Smart only versions
MTL5051 Serial-data comms isolator   Continues as MTL5051 model
MTL5053 Fieldbus isolator/power supply   Discontinued
MTL5061 Fire/smoke detector interface MTL5561  
MTL5073 Temperature converter MTL5575 Now with trip alarm
MTL5074 Temperature converter MTL5575 Now with trip alarm
MTL5081 mV/THC isolator MTL5581  
MTL5082 Resistance isolator MTL5582  
MTL5113P Failsafe sw/prox interface MTL5501-SR  
MTL5314 Trip amplifier   Continues as MTL5314 model
MTL5344 Repeater power supply   Discontinued
MTL5349 Isolating driver   Discontinued
MTL5991 24V power supply   Continues as MTL5991 model
MTL5995 Fieldbus power supply   Convert to F10X range product



We are specialized in intelligent instruments, including : control system, transmitters, flow meters,sensors, recorders, analyzers, control valves, controllers, PLC's, etc.
 
We mainly supply Yokogawa ,Honeywell,Siemens,ABB,FLUKE,Endress+Hauser,Schneider Electric,Moeller,FUJI,Omron,Pepperl+Fuchs,Hima,Yaskawa, Norgren, Hach, Weidmuller ,Phoenix,MTL,Testo etc.
 
Why choose us?
 
1. 100% original product, 100% quality assurance.
If you find a fake. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
 
2. Varied payment methods.
We adopt T/T, western union and paypal. If you can not trust us , you can choose to pay it via Aliexpress! 100% make your money safe!
 
3.SHIPPING:
We can shipping all over the world.via DHL,UPS,Fedex,TNT and EMS etc., the packaging is very safe and strong. if you have any special needs,please notify me.
It will take 3 to 7days to reach in your hands.
 
Packaging: 
Imported with original packaging or standard export packing.Customize design is acceptable.
 
Contact:
 
HONGKONG XIEYUAN TECH CO., LIMITED
Email:becky@hkxytech.com   Web:www.hkxytech.com
Mobile:+86-15972186287(Whatsapp & Wechat) 


 

Previous:MTL7728+ Shunt-diode Safety Barrier MTL7728+ Zener Barrier A Next:MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repea
 Footer begin -->