MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repeat RTD Signals
The MTL5582 connects to a 2-, 3-, or 4-wire resistance temperature device (RTD) or other resistance located in a hazardous area, isolates it and repeats the resistance to a monitoring system in the safe area. The module is intended typically (but not exclusively) for use with Pt100 3-wire RTDs. Switches enable selection of 2-, 3-, or 4-wire RTD connection. The MTL5582 should be considered as an alternative, nonconfigurable MTL5575, for use in RTD applications where a resistance input is preferred or needed instead of 4/20mA. The design is notable for its ease of use and repeatability. The number of wires which can be connected on the safe-area side of the unit is independent of the number of wires which can be connected on the hazardous-area side. The module drives upscale in the case of open circuit detection. Note that this module is not suitable for use with measurement systems where the resistance input channels are multiplexed.
Temperature Input module of MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repeat RTD Signals
These modules accept inputs from low-level dc sources such as thermocouples or RTDs in hazardous
areas and converts them into 4/20mA signals to drive safe area loads.
Early burnout detection (EBD) of MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repeat RTD Signals
When EBD is selected, the resistance of the thermocouple circuit is monitored and an alarm is
raised when there is an increase of more than 50m. This enables preventative maintenance to be
conducted on the field installation before the thermocouple actually breaks.
Configuration using PCS45/PCL45USB of MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repeat RTD Signals
Use PCS45 software, in conjunction with the PCL45USB serial link, to configure these modules. Instructions
are contained within the software.
MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repeat RTD Signals
Single channel, to repeat RTD signals
The MTL5582 connects to a 2-, 3-, or 4-wire resistance temperature device (RTD) or other resistance located in a hazardous area, isolates it and repeats the resistance to a monitoring system in the safe area. The module is intended typically (but not exclusively) for use with Pt100 3-wire RTDs. Switches
enable selection of 2-, 3-, or 4-wire RTD connection. The MTL5582 should be considered as an alternative, non-configurable MTL5575, for use in RTD applications where a resistance input is preferred or needed instead of 4/20mA. The design is notable for its ease of use and repeatability.
The number of wires which can be connected on the safe-area side of the unit is independent of the number of wires which can be connected on the hazardous-area side. The module drives upscale in the case of open circuit detection.
MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repeat RTD Signals
•Compact modular design with DIN rail mounting
•High packing density
•Single and multi-channel I/O modules
•3-port isolation with low power dissipation
•Compatible with MTL5000
MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repeat RTD Signals
Part Number of MTL5500 Series
MTL5501-SR, MTL5510, MTL5510B, MTL5511, MTL5513, MTL5514, MTL5514D, MTL5516C, MTL5517, MTL5521, MTL5522, MTL5523, MTL5523V, MTL5523VL, MTL5524, MTL5525, MTL5526, MTL5531, MTL5532, MTL5533, MTL5541, MTL5541A, MTL5541AS, MTL5541S, MTL5544, MTL5544A, MTL5544AS, MTL5544D, MTL5544S, MTL5546, MTL5546Y, MTL5549, MTL5549Y, MTL5561, MTL5575, MTL5576-RTD, MTL5576-THC, MTL5581, MTL5582
MTL5582 Safety Barriers MTL5582 Resistance Isolator to Repeat RTD Signals
MTL5000 | Function | MTL5500 | Notes |
MTL5011B | 1ch, changeover relay output | MTL5511 | |
MTL5012 | 1ch, solid-state output | Use 1ch of MTL5513 | |
MTL5012S | 1ch, solid-state output, UE1 special | No replacement | |
MTL5014 | 1ch, c/o relay output, LFD relay | MTL5514/14D |
MTL5514 does not provide 1in 2out function. MTL5514D with 1in 2out available Q1 2014 |
MTL5015 | 2ch, solid-state output | MTL5513 |
Common connection on haz side, max frequency response 500Hz |
MTL5016 | 2ch, n/o relay output | MTL5516C | |
MTL5017 | 2ch, n/o relay output, LFD relay | MTL5517 | LFD relay energises on alarm |
MTL5018 | 2ch, changeover relay output | MTL5516C | Common connection on haz side |
MTL5018ac | 2ch, changeover relay output, ac power |
Continues as MTL5018ac. Alternative option: MTL5516C fitted with MPA5500 ac adaptor |
|
MTL5021 | Loop powered, IIC, (12.85V, 45mA, cl 45mA) | MTL5521 | (12.8V, 48mA, cl 48mA) |
MTL5022 | Loop powered, IIB, (12.9V, 60mA, cl 60mA) | MTL5522 | (9.9V, 70mA, cl 70mA) |
MTL5023 | Logic ctrl, lfd, phase,(12.85V, 45mA, cl 45mA) | MTL5523 | (12.8V, 48mA, cl 48mA) |
MTL5024 | Logic ctrl, phase, (12.85V, 45mA, cl 45mA) | MTL5524 | (12.8V, 48mA, cl 48mA) |
MTL5025 | Loop powered, IIC, (8.6V, 45mA, cl 45mA) | MTL5525 | (7V, 48mA, cl 48mA), lower Io |
MTL5031 | Vibration transducer interface | MTL5531 | Now Velomitor compatible |
MTL5032 | Pulse isolator | MTL5532 | Now with 4-20mA output and alarm |
MTL5040 | Loop isolator | Use MTL5541 and MTL5546Y | |
MTL5041 | For 2-wire transmitters | MTL5541 | |
MTL5042 | For 2- or 3-wire txs, smart | MTL5541 | |
MTL5043 | Dual output for 2-wire smart txs | MTL5544D | No current sink o/p. Passive Tx input |
MTL5044 | Two channel for 2-wire txs | MTL5544 | Now with passive Tx inputs |
MTL5045 | Isolating driver | MTL5546Y | Smart only versions |
MTL5046 | Smart isolating driver with LFD | MTL5546 | |
MTL5049 | Two channel isolating driver | MTL5549Y | Smart only versions |
MTL5051 | Serial-data comms isolator | Continues as MTL5051 model | |
MTL5053 | Fieldbus isolator/power supply | Discontinued | |
MTL5061 | Fire/smoke detector interface | MTL5561 | |
MTL5073 | Temperature converter | MTL5575 | Now with trip alarm |
MTL5074 | Temperature converter | MTL5575 | Now with trip alarm |
MTL5081 | mV/THC isolator | MTL5581 | |
MTL5082 | Resistance isolator | MTL5582 | |
MTL5113P | Failsafe sw/prox interface | MTL5501-SR | |
MTL5314 | Trip amplifier | Continues as MTL5314 model | |
MTL5344 | Repeater power supply | Discontinued | |
MTL5349 | Isolating driver | Discontinued | |
MTL5991 | 24V power supply | Continues as MTL5991 model | |
MTL5995 | Fieldbus power supply | Convert to F10X range product |
We are specialized in intelligent instruments, including : control system, transmitters, flow meters,sensors, recorders, analyzers, control valves, controllers, PLC's, etc.
We mainly supply Yokogawa ,Honeywell,Siemens,ABB,FLUKE,Endress+Hauser,Schneider Electric,Moeller,FUJI,Omron,Pepperl+Fuchs,Hima,Yaskawa, Norgren, Hach, Weidmuller ,Phoenix,MTL,Testo etc.
Why choose us?
1. 100% original product, 100% quality assurance.
If you find a fake. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt T/T, western union and paypal. If you can not trust us , you can choose to pay it via Aliexpress! 100% make your money safe!
3.SHIPPING:
We can shipping all over the world.via DHL,UPS,Fedex,TNT and EMS etc., the packaging is very safe and strong. if you have any special needs,please notify me.
It will take 3 to 7days to reach in your hands.
Packaging:
Imported with original packaging or standard export packing.Customize design is acceptable.
Contact:
HONGKONG XIEYUAN TECH CO., LIMITED
Email:becky@hkxytech.com Web:www.hkxytech.com
Mobile:+86-15972186287(Whatsapp & Wechat)